TelePole WR/ Operating & Maintenance Manual Page 23
Speaker Circuit (U13)
The speaker circuit is activated in the following cases:
a. Threshold level exceeding.
b. Malfunction.
c. Push-button pressing approval.
d. The speaker clicks frequency is proportional to the radiation field intensity.
A 3 KHz signal on pin U13/3 activates the speaker. Two ports control the speaker:
Port 1 - alarm, pin U3/9
Port 2 - speaker on, pin U3/19
For threshold level exceeding and malfunction:
U3/9 - 0
U3/19 -
1sec 1sec
For push-button pressing approval:
U3/9 - 0
U3/19 -
100msec
For clicks activation in relation to the radiation field intensity:
U3/9 - 1
U3/19 - 1
To mute the speaker:
U3/9 - 0.
U3/19 - 1
Input & Output Latch
Two 74HC373 ICs are used for the input/output signals. The ICs are connected to the
CPU BUS.
Input signals - U9, address - 8200H
Output signals - U3, address - 8100H
Output Signals
0 - U3/2 external/internal detector (optional)
1 - U3/5 low range / high range geiger
2 - U3/6 Electro-luminescence
3 - U3/9 speaker alarm
4 - U3/12 not in use
5 - U3/15 not in use
6 - U3/16 enables VCC for barcode laser reader
7 - U3/19 speaker on